Devices to prevent pollution by backflow of potable water - In-line anti-vacuum valves DN 10 to DN 50 inclusive - Family D, type A

This document specifies the field of application, the dimensional, the physico-chemical, the design, the hydraulic, the mechanical, and the acoustic characteristics of in-line anti vacuum valve family D Type A.
This document covers in-line anti vacuum valve family D Type A, intended to prevent pollution of potable water by backflow, caused by backsiphoning only.
It is applicable to in-line anti vacuum valve in denominations DN 10 up to DN 50.
It covers in-line anti vacuum valve of PN 10 that are capable of working without modification or adjustment:
-   at any pressure, up to 1 MPa (10 bar);
-   with any pressure variation, up to 1 MPa (10 bar);
-   in permanent duty at a limited temperature of 65 °C and for maximum 1 h at 90 °C.
It specifies also the test methods and requirements for verifying their characteristics, the marking and the presentation at delivery.

Sicherungseinrichtungen zur Verhütung von Trinkwasserverunreinigung durch Rückfließen - Rohrleitungsbelüfter DN 10 bis einschließlich DN 50 - Familie D, Typ A

Dieses Dokument legt den Anwendungsbereich, die maßlichen, physikalisch-chemischen, Auslegungs-, hydraulischen, mechanischen und akustischen Eigenschaften der Rohrleitungsbelüfter Familie D, Typ A fest.
Dieses Dokument gilt ausschließlich für Rohrleitungsbelüfter Familie D, Typ A, die zur Verhütung von Trinkwasserverunreinigungen durch Rückfließen, verursacht durch Rücksaugen, vorgesehen sind.
Es gilt für Rohrleitungsbelüfter der Bezeichnungen DN 10 bis DN 50.
Es behandelt Rohrleitungsbelüfter mit PN 10, die ohne Abänderung oder Nachstellung funktionsfähig sind:
- bei Druckwerten, bis 1 MPa (10 bar);
- bei Druckschwankungen, bis 1 MPa (10 bar);
- im Dauerbetrieb bei einer Grenztemperatur von 65 °C und für maximal 1 h bei 90 °C.
Es legt zudem die Prüfverfahren und Anforderungen zur Verifizierung ihrer Eigenschaften, der Kennzeichnung und der Bereitstellung bei der Auslieferung fest.

Dispositifs de protection contre la pollution de l'eau potable par retour - Soupape anti-vide en ligne DN 10 à DN 50 inclus - Famille D, type A

Le présent document spécifie le domaine d’application ainsi que les caractéristiques dimensionnelles, physico-chimiques, de conception, hydrauliques, mécaniques et acoustiques des soupapes anti-vide en ligne de la famille D, type A.
Le présent document couvre uniquement les soupapes anti-vide en ligne de la famille D, type A, destinées à éviter la pollution de l’eau potable par retour, provoquée par siphonnage.
Il s’applique aux soupapes anti-vide en ligne de dénomination DN 10 à DN 50.
Il couvre les soupapes anti-vide en ligne de PN 10 qui, sans modification ni ajustement, peuvent fonctionner :
- à n’importe quelle pression, jusqu’à 1 MPa (10 bar) ;
- sous n’importe quelle variation de pression, jusqu’à 1 MPa (10 bar) ;
- de manière ininterrompue jusqu’à une température limite de 65 °C, et pendant 1 h, au maximum, à 90 °C.
Il spécifie également les méthodes d’essai et les exigences permettant de contrôler leurs caractéristiques, le marquage et la présentation à la livraison.

Naprave za varovanje pred onesnaženjem pitne vode zaradi povratnega toka - Ventili za preprečevanje podtlaka DN 10 do DN 50 - Družina D, tip A

General Information

Status
Published
Publication Date
23-Jun-2020
Withdrawal Date
30-Dec-2020
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
24-Jun-2020
Due Date
15-Nov-2020
Completion Date
24-Jun-2020

Relations

Buy Standard

Standard
EN 14451:2020
English language
22 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 14451:2020
01-september-2020
Nadomešča:
SIST EN 14451:2005
Naprave za varovanje pred onesnaženjem pitne vode zaradi povratnega toka -
Ventili za preprečevanje podtlaka DN 10 do DN 50 - Družina D, tip A
Devices to prevent pollution by backflow of potable water - In-line anti-vacuum valves DN
10 to DN 50 inclusive - Family D, type A
Sicherungseinrichtungen zur Verhütung von Trinkwasserverunreinigung durch
Rückfließen - Rohrleitungsbelüfter DN 10 bis einschließlich DN 50 - Familie D, Typ A
Dispositifs de protection contre la pollution de l'eau potable par retour - Soupape anti-
vide en ligne DN 10 à DN 50 inclus - Famille D, type A
Ta slovenski standard je istoveten z: EN 14451:2020
ICS:
13.060.20 Pitna voda Drinking water
23.060.50 Blokirni ventili Check valves
91.140.60 Sistemi za oskrbo z vodo Water supply systems
SIST EN 14451:2020 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 14451:2020

---------------------- Page: 2 ----------------------
SIST EN 14451:2020


EN 14451
EUROPEAN STANDARD

NORME EUROPÉENNE

June 2020
EUROPÄISCHE NORM
ICS 13.060.20; 23.060.50 Supersedes EN 14451:2005
English Version

Devices to prevent pollution by backflow of potable water
- In-line anti-vacuum valves DN 10 to DN 50 inclusive -
Family D, type A
Dispositifs de protection contre la pollution de l'eau Sicherungseinrichtungen zur Verhütung von
potable par retour - Soupape anti-vide en ligne DN 10 à Trinkwasserverunreinigung durch Rückfließen -
DN 50 inclus - Famille D, type A Rohrleitungsbelüfter DN 10 bis einschließlich DN 50 -
Familie D, Typ A
This European Standard was approved by CEN on 24 May 2020.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14451:2020 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
SIST EN 14451:2020
EN 14451:2020 (E)
Contents Page
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 Nominal size . 7
5 Designation. 7
6 Marking and technical documents . 8
6.1 General . 8
6.2 Marking .
...