Acoustics - Test code for drywall systems of plasterboard with steel studs - Airborne sound insulation

This draft European Standard specifies additional information necessary to carry out efficiently and under standardized conditions the determination of the sound reduction index of drywall systems of plasterboard with steel studs according to EN ISO 10140-2 “Acoustics — Laboratory measurement of sound insulation of building elements — Part 2: Measurement of airborne sound insulation”. It specifies the additional requirements of the sound reduction measurements, the operating and mounting conditions that shall be used for the test and additional test report information to be reported. Observe that all demands in EN ISO 10140-2 still must be fulfilled. The results obtained are used to convert frequency-dependent sound reduction index into single number ratings, according to EN ISO 717-1. These performances can be used to compare different products, or, and to express a requirement, or, and as input into estimation methods, such as the series EN 12354-1.

Akustik - Prüfvorschrift für Trockenwandsysteme aus Metallständerwänden mit Gipskartonbeplankung - Messung der Luftschalldämmung

Dieser europäische Normentwurf legt zusätzliche Angaben fest, die für die effiziente Durchführung der Bestimmung des Schalldämm-Maßes von Trockenwandsystemen aus Gipsplatten mit Stahlständern nach EN ISO 10140 2 “Akustik — Messung der Schalldämmung von Bauteilen im Prüfstand — Teil 2: Messung der Luftschalldämmung“ unter genormten Bedingungen erforderlich sind. Er legt die zusätzlichen Anforderungen an die Messungen der Schalldämmung, die für die Prüfung anzuwendenden Betriebs- und Befestigungsbedingungen sowie zusätzliche, im Prüfbericht anzugebende Informationen fest. Es ist zu beachten, dass weiterhin alle Anforderungen der EN ISO 10140 2 erfüllt werden müssen. Die erhaltenen Ergebnisse werden genutzt, um das frequenzabhängige Schalldämm-Maß in Einzahl-Bewertungen nach EN ISO 717 1 umzuwandeln. Diese Leistungsfaktoren können genutzt werden, um verschiedene Produkte miteinander zu vergleichen und/oder um Anforderungen anzugeben und/oder als Eingabedaten für Schätzverfahren wie z. B. EN 12354 1.

Acoustique - Code d'essai pour systèmes de cloisons sèches en plaques de plâtre avec montants en acier - Mesure de l'affaiblissement aérien

La présente Norme européenne fournit les informations complémentaires à l'EN ISO 10140-1 nécessaires pour déterminer de manière efficace et dans des conditions normalisées l'indice d'affaiblissement acoustique de systèmes de cloisons sèches en plaques de plâtre avec montants en acier conformément à l'EN ISO 10140-2, « Acoustique — Mesurage en laboratoire de l'isolation acoustique des éléments de construction — Partie 2 : Mesurage de l'isolation au bruit aérien ». Noter qu'il convient que toutes les exigences de l'EN ISO 10140-2 soient encore satisfaites. Afin de réduire l'incertitude, elle spécifie :
-   des lignes directrices supplémentaires pour l'essai de systèmes de cloisons sèches en plaques de plâtre avec montants en acier ;
et
-   une méthode de validation du laboratoire en utilisant deux cloisons d'essai de référence.
Les résultats obtenus sont utilisés pour convertir les indices d'affaiblissement acoustique par fréquence en valeurs globales, conformément à l'EN ISO 717-1. Ces performances peuvent être utilisées pour comparer différents produits et/ou pour exprimer une exigence et/ou comme données d'entrée dans des méthodes d'estimation telles que l'EN 12354-1.

Akustika - Preskusni postopek za suhomontažne sisteme iz mavčno-kartonskih plošč s kovinsko konstrukcijo - Izolirnost pred zvokom v zraku

Ta osnutek evropskega standarda določa dodatne informacije, potrebne za učinkovito določitev zvočne izolirnosti suhomontažnih sistemov iz mavčno-kartonskih plošč s kovinsko konstrukcijo pod standardiziranimi pogoji v skladu s standardom EN ISO 10140-2: Akustika - Laboratorijsko merjenje zvočne izolirnosti gradbenih elementov - 2. del: Merjenje izolirnosti pred zvokom v zraku. Določa dodatne zahteve za meritve zvočne izolirnosti, zahteve za delovanje in priključitev, ki jih je treba uporabiti za preskus, ter dodatne informacije, ki jih mora vključevati poročilo o preskusu. Upoštevati je treba, da morajo biti še vedno izpolnjene vse zahteve standarda EN ISO 10140-2. Dobljeni rezultati se uporabijo za pretvorbo indeksa zvočne izolirnosti, odvisnega od frekvence, v enoštevilčne podatke v skladu s standardom EN ISO 717-1. Te lastnosti se lahko uporabijo za primerjavo različnih proizvodov ali/in za izražanje zahteve ali/in kot vhod v metode vrednotenja (npr. skupina standardov EN 12354-1).

General Information

Status
Published
Public Enquiry End Date
29-Apr-2014
Publication Date
11-Nov-2015
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
06-Oct-2015
Due Date
11-Dec-2015
Completion Date
12-Nov-2015

Buy Standard

Standard
EN 16703:2015 - BARVE
English language
28 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 16703:2014
English language
27 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.DUWRQVNLKAkustik - Prüfvorschrift für Trockenwandsysteme aus Metallständerwänden mit Gipskartonbeplankung - Messung der LuftschalldämmungAcoustique - Code d'essai pour systèmes de cloisons sèches en plaques de plâtre avec montants en acier - Mesure de l'affaiblissement aérienAcoustics - Test code for drywall systems of plasterboard with steel studs - Airborne sound insulation91.120.20L]RODFLMDAcoustics in building. Sound insulation91.060.10Stene. Predelne stene. FasadeWalls. Partitions. FacadesICS:Ta slovenski standard je istoveten z:EN 16703:2015SIST EN 16703:2015en,fr,de01-december-2015SIST EN 16703:2015SLOVENSKI
STANDARD



SIST EN 16703:2015



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 16703
September
t r s w ICS
{ sä r x rä s râ
{ sä s t rä t r English Version
Acoustics æ Test code for drywall systems of plasterboard with steel studs æ Airborne sound insulation Acoustique æ Code d 5essai pour systèmes de cloisons sèches en plaques de plâtre avec montants en acier æ Mesure de l 5affaiblissement aérien
Akustik æ Prüfvorschrift für Trockenwandsysteme aus Metallständerwänden mit Gipsplattenbeplankung æ Messung der Luftschalldämmung This European Standard was approved by CEN on
z August
t r s wä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey and United Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
9
t r s w CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s x y r uã t r s w ESIST EN 16703:2015



EN 16703:2015 (E) 2 Contents European foreword . 4 Introduction . 5 1 Scope . 6 2 Normative references. 6 3 Terms and definitions . 6 4 Test code for drywall systems of plasterboard with steel studs . 7 4.1 Application . 7 4.2 Testing Guidelines . 7 4.2.1 Test element . 7 4.2.2 Boundary and mounting conditions . 7 4.2.3 Test report . 8 4.3 Validation of the laboratory with two reference test partitions . 8 4.3.1 Test elements . 8 4.3.2 Acceptance criteria . 8 4.3.3 Remedial investigation . 10 4.4 Application of uncertainties . 11 Annex A (normative)
Reference test partition location in aperture . 12 A.1 General . 12 A.2 Case A “Aperture without niche and one acoustic break” . 12 A.3 Case B “Aperture without niche and two acoustic breaks with Ratio 2:1”. 13 A.4 Case C “Aperture with niche and one acoustic break” . 13 Annex B (normative)
Reference test partition Type 1 . 14 B.1 Description of Reference test partition Type 1 . 14 B.1.1 Single Framework, single board layer partition . 14 B.2 Installation procedure of partition Type 1 . 15 B.2.1 Installation of framework with channels and studs . 15 B.2.2 Installation of plasterboards 1st side . 16 B.2.3 Installation of insulation in cavity . 16 B.2.4 Installation of plasterboards 2nd side . 16 B.2.5 Jointing for both sides of the partition . 16 Annex C (normative)
Reference test partition Type 2 . 18 C.1 Twin framework, double board layer partition . 18 C.1.1 General . 18 C.1.2 Installation of framework with channels and studs . 19 C.2 Installation of plasterboards . 20 C.2.1 General . 20 SIST EN 16703:2015



EN 16703:2015 (E) 3 C.2.2 Plasterboard inner layer on first side . 20 C.2.3 Plasterboard outer layer on first side . 20 C.3 Installation of insulation in cavity . 21 C.4 Installation of plasterboards 2nd side - Plasterboard inner layer on second side . 21 C.5 Plasterboard outer layer on second side . 21 C.6 Jointing for both sides of the partition . 21 Annex D (informative)
Interlaboratory Tests performed for the development of this Test Code standard . 22 Annex E (informative)
E Modulus - Control Method (static E Modulus with 3 bending points) . 24 Annex F (informative)
E Modulus - Expertise Method (dynamic E Modulus) . 25 Bibliography . 27
SIST EN 16703:2015



EN 16703:2015 (E) 4 European foreword This document (EN 16703:2015) has been prepared by Technical Committee CEN/TC 126 “Acoustic properties of building elements and of buildings”, the secretariat of which is held by AFNOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by March 2016, and conflicting national standards shall be withdrawn at the latest by March 2016. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This standard is a complement to the European Standard EN ISO 10140-1 and is not intended to replace it. The complement includes more stringent rules, narrower tolerances and new, additional requirements. According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 16703:2015



EN 16703:2015 (E) 5 Introduction Product standard EN 520:2004+A1:2009 “Gypsum plasterboards – Definitions, requirements and test methods” specifies requirements and test methods and establishes how to declare characteristics and to affix the CE marking of products accordingly. In EN 520:2004+A1:2009, when a drywall partition with plasterboard and steel studs has an airborne sound insulation performance property, its sound reduction should be determined in accordance with EN ISO 140-3, now replaced by EN ISO 10140-2. The measured sound reductions are calculated into sound reduction index R, in third octave bands and into single number indexes, in accordance with EN ISO 717-1. Those single number ratings are used for the CE marking. Measurement of sound reduction according to EN ISO 10140-2 was known through earlier inter laboratory tests (ILT), to generate large spread in results from different laboratories. This was not suitable, either from a competition point of view or from an end-user perspective. Therefore, CEN/TC 126 “Acoustic properties of building elements and of buildings” decided to set up a working group, WG 9 “Test Code for drywall partition with plasterboard and steel studs”, with the scope to improve reproducibility by developing a Test Code complementary to the EN ISO 10140-1. One part of this work was to organize ILT for sound reduction measurements, to assess the uncertainty of acoustic quantities (Annex D). This was used by the working group to prepare this test code for drywall systems, including guidelines of testing installation and validation of laboratory, to decrease the level of uncertainty. SIST EN 16703:2015



EN 16703:2015 (E) 6 1 Scope This European Standard specifies information additional to EN ISO 10140-1 necessary to carry out efficiently and under standardized conditions the determination of the sound reduction index of drywall systems of plasterboard with steel studs according to EN ISO 10140-2 “Acoustics — Laboratory measurement of sound insulation of -building elements — Part 2: Measurement of airborne sound insulation”. Observe that all demands in EN ISO 10140-2 should still be fulfilled. In order to decrease the uncertainty, it specifies: — additional guidelines for testing drywall systems of plasterboard with steel studs; and — a method to validate laboratory by using two reference test partitions. The results obtained are used to convert frequency-dependent sound reduction index into single number ratings, according to EN ISO 717-1. These performances can be used to compare different products, or, and to express a requirement, or, and as input into estimation methods, such as EN 12354-1. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 520:2004+A1:2009, Gypsum plasterboards — Definitions, requirements and test methods EN 13162, Thermal insulation products for buildings — Factory made Mineral wool (MW) products — Specification EN 13963, Jointing materials for gypsum boards — Definitions, requirements and test methods EN 14195, Metal framing components for gypsum board systems — Definitions, requirements and test methods EN 14566, Mechanical fasteners for gypsum plasterboard systems — Definitions, requirements and test methods EN ISO 10140 (all parts), Acoustics — Laboratory measurement of sound insulation of building elements (ISO 10140, all parts) 3 Terms and definitions For the purposes of this document, the following term and definition apply. 3.1 drywall system of plasterboard with steel studs partition comprising a non load bearing metal frame partition enclosed by plasterboards SIST EN 16703:2015



EN 16703:2015 (E) 7 4 Test code for drywall systems of plasterboard with steel studs 4.1 Application 4.1.1 This standard applies to non-load bearing metal frame partition comprising a metal frame enclosed by plasterboards. In general, the type, size, gauge and spacing of the studs, and the size, type and number of layers of plasterboard and eventual amount and type of cavity filling material in partition constructions are determined by the performance requirements of the system. 4.1.2 The quantity to be determined is the sound reduction index R as a function of frequency. The definition of R is given in EN ISO 10140-2. 4.2 Testing Guidelines 4.2.1 Test element The partition size shall be between 9 m2 – 12 m2. For all others information, refer to EN ISO 10140-1 and EN ISO 10140-2. 4.2.2 Boundary and mounting conditions 4.2.2.1 General rules The test element shall be mounted directly on the facilities frame; it shall not be a prefabricated full partition. The test element should be installed in a similar manner to the actual construction with careful simulation of typical connections and sealing conditions at the perimeter and at all joints. 4.2.2.2 Perimeters mounting A gap of about 5 mm to 10 mm shall remain between the plasterboards and the reveal of the test opening. This gap shall be filled with appropriate material. Drying time has to respect product instruction according to 4.3.1 because the type of filler will have an influence on the performance of the partition. Cracks in the perimeter may occur, resulting in air leakage. To control risk a procedure shall be set in the laboratory to check this. This shall be at minimum a visual control but can also be any additional method. 4.2.2.3 Partition positions The sound reduction index of drywall system of plasterboard with steel studs is influenced by the mounting conditions in the test opening of the laboratory. Important installation parameters include the niche depth and the position of the partition in relation to the acoustic break in the test aperture. The partition shall be installed into the test opening so that the niches on both sides of the partition have different depths with a ratio of 2:1. To improve the reproducibility between laboratories and facilitate comparison of sound reduction indices for different drywall system of plasterboard with steel studs, the partition (even double wall) shall not be mounted across the acoustic break between sending and receiving room of the laboratory, but on the same side of the break as indicated in Annex A. Main mounting conditions are reported in Annex A; others may be used but shall be fully described in the test report. SIST EN 16703:2015



EN 16703:2015 (E) 8 NOTE Mounting the lightweight partition with one leaf on one side and the other leaf on the other side of the acoustic break can result in higher values for the sound reduction index. Other mounting conditions may be suitable for certain types of twin leaf walls, for example, walls for semidetached houses where the leaves are vibrationally uncoupled (for example on separate foundations). In such cases the wall leaves can be mounted on each side of the acoustic break. No absorption material should be located close (less than 1 m) to the perimeter of the partition. The acoustic break has to be covered with soft reflecting materials. 4.2.3 Test report The test report shall include the information listed in EN ISO 10140-2:2010, Clause 9 and the following additional information shall also be reported: a) detailed description of the perimeters treatments; b) detailed description of the putty used and its drying time; c) detailed description of the fasteners used (screws spacing, stud centre) including perimeter frame; d) detailed description of the partition position ; it is recommended to refer to Annex A. 4.3 Validation of the laboratory with two reference test partitions 4.3.1 Test elements To reduce expanded uncertainty in a reproducibility condition of drywall plasterboard partition with steel stud, it is required to conduct preliminary tests with two laboratory reference test partitions described in Annexes B and C. The materials used to conduct these reference test partition tests should be products in accordance with the properties reported in Tables B.1 and C.1. The properties of the products mentioned shall be measured using the methods within the relevant product standard except for the E-modulus properties. The position of the reference test partitions shall be in accordance with Annex A. The installation of the reference test partitions shall be in accordance with the Annex B (partition type 1) and Annex C (partition type 2). The measurement shall be done at least 12 h after installation in accordance with EN ISO 10140-2. 4.3.2 Acceptance criteria 4.3.2.1 General Tables 1 and 2 define the envelope of partition type 1 and type 2 respectively. The acceptance criteria is met if the measured spectra for both reference test partitions are within the envelopes presented below or the sum over all third octave bands of the deviations between the measured and the envelope values does not exceed 4 dB (see 4.4 for further information on uncertainty values and how to apply). The deviation of 4 dB has been decided to take into account modal behaviours in low frequency and where critical frequency has influenced the sound reduction. This has been observed to be influenced by both laboratory configuration origin and plasterboard stiffness. If the local minimum around the critical frequency is not in the 3150 Hz third octave band, it is recommended to control the value of the E modulus of the plasterboard to be close to the ones that have been tested initially for the laboratory SIST EN 16703:2015



EN 16703:2015 (E) 9 qualification (± 20 % of the properties mentioned in Table D.1). The E-modulus could be measured indifferently with one of the two methods proposed in Annexes E and F. 4.3.2.2 Envelope for partition type 1 Table 1 — Min and Max values of the sound reduction index R of the reference test partition type 1 frequency (Hz) Rmin (dB) Rmax. (dB)
50 10,3 21,5
63 8,9 19,5
80 8,1 17,0
100 12,3 16,8
125 20,1 25,0
160 27,9 32,2
200 32,2 35,2
250 34,0 38,6
315 38,3 42,2
400 42,2 46,0
500 44,9 49,9
630 47,2 52,2
800 49,6 55,8
1 000 50,9 60,2
1 250 51,5 63,0
1 600 52,3 63,6
2 000 51,2 60,9
2 500 42,2 48,7
3 150 39,9 44,8
4 000 44,1 48,8
5 000 47,4 52,4 SIST EN 16703:2015



EN 16703:2015 (E) 10 4.3.2.3 Envelope for partition type 2 Table 2 — Min and Max values of the sound reduction index R of the reference test partition 2 Frequency (Hz) Rmin (dB) Rmax. (dB)
50 19,2 26,4
63 21,8 30,6
80 30,9 35,5
100 37,0 41,4
125 41,0 45,0
160 44,3 50,3
200 49,2 53,8
250 52,8 57,6
315 55,1 60,6
400 59,0 65,0
500 61,3 68,6
630 62,8 70,3
800 64,6 71,9
1 000 66,2 75,3
1 250 67,9 77,8
1 600 69,2 79,7
2 000 68,8 79,0
2 500 60,4 72,1
3 150 60,1 71,8
4 000 62,0 74,6
5 000 62,8 75,5 4.3.3 Remedial investigation If the measurement results do not meet the given criteria then the analysis of the interlaboratory test organized in 2010 (Annex D) suggests that the following reasons should be investigated: — diffusivity (please refer to the EN ISO 10140-5:2010, 3.2.2); — flanking transmission, in particular for partition type 2 (please refer to the EN ISO 10140-5:2010, 3.2.5). NOTE Other parameters like changing loudspeaker and microphone positions can be a way to reach the criteria. These remedial actions should be applicable for both reference test partitions and shall be applied for all further testing. SIST EN 16703:2015



EN 16703:2015 (E) 11 4.4 Application of uncertainties If the testing guidelines are applied, the laboratory is validated as above and the acceptance criteria for the two reference test partitions are met then the standard uncertainties values given in the table below can be applied. Table 3 — Standard uncertainties u of single number quantities Single number Standard uncertainty in a reproducibility condition u (dB) Rw 0,7 Rw+C 0,7 Rw+C tr 1,1 For measurement results obtained in accordance with the EN ISO 10140 (all parts), the expanded uncertainty U shall be calculated by: U = k u [1] where U is the expanded uncertainty calculated for a given confidence level for the two-sided test 95 %; u is the standard uncertainty determined in Table 3 of this standard; and k is the coverage factor. Its value depends on the distribution of the possible values of the measure and on the confidence level.
For the purpose of this standard it is assumed that the values of the k = 2. A measurement result shall then be stated as follows: Y = y ± U [2] where Y is the measurand (Rw, Rw+C, Rw+Ctr); y the best estimate found by the measurement; U is the expanded uncertainty calculated for a given confidence level for the two-sided test 95 %.
For more information about handling uncertainty refer to ISO 12999-1. SIST EN 16703:2015



EN 16703:2015 (E) 12 Annex A (normative)
Reference test partition location in aperture A.1 General This annex has two objectives: — to define with precision the location of the partition when validating the laboratory with the two reference test partitions; — to simplify the description of the partition's location in test report. To ensure a good reproducibility the specimen has to be installed on source side, and its location has to be reported with the letters representing the following privileged configuration. A.2 Case A “Aperture without niche and one acoustic break” Case A is the configuration with an aperture without a niche and with one acoustic break; see Figure A.1.
Key 1 source room 2 receiving room 3 acoustic break airtight layer materials 4 acoustic break of the laboratory Figure A.1 — Sketch of specimen location case A SIST EN 16703:2015



EN 16703:2015 (E) 13 A.3 Case B “Aperture without niche and two acoustic breaks with Ratio 2:1” Case B is the configuration with an aperture without a niche and with two acoustic breaks; see Figure A.2.
Key 1 source room 2 receiving room 3 acoustic break airtight layer materials 4 acoustic break of the laboratory Figure A.2 — Sketch of specimen location case B A.4 Case C “Aperture with niche and one acoustic break” Case C is the configuration with an aperture with a niche and with one acoustic break; see Figure A.3. In case where the application of the rules 2:1 makes the partition locate on the acoustic break, then move the partition to the source side of the break.
Key 1 source room 2 receiving room 3 acoustic break airtight layer materials 4 acoustic break of the laboratory Figure A.3 — Sketch of specimen location case C SIST EN 16703:2015



EN 16703:2015 (E) 14 Annex B (normative)
Reference test partition Type 1 B.1 Description of Reference test partition Type 1 B.1.1 Single Framework, single board layer partition The partition consists of a 70 mm metal stud single framework with studs at 600 mm centres, 70 mm insulation in the cavity and a single layer of 12,5 mm plasterboard on each side of the framework, see Figure B.1. When acquiring the reference test partition materials, the laboratory selects materials respecting the reference properties presented in Table B.1. If difficulty occurs it is suggested to refer to the local technical assistance of the manufacturer. Table B.1 — Material list and essential properties Product Dimensions Product standard Essential properties
Plasterboard with tapered edge 3000 mm × 1200 mm × 12,5 mm EN 520:2004+A1:2009 Surface mass 8,9 kg/m2 to 9,4 kg/m2 U-70–30/6 Channel 30 mm x70 mm × 30 mm EN 14195 Steel gauge 0,54 mm to 0,59 mm C-70–35/6 Studs 34 mm × 69 mm × 36 mm EN 14195 Steel gauge 0,54 mm to 0,59 mm Screw 3,5 mm × 25 mm EN 14566 / / Screw Diameter 6 mm
/ / Self-adhesive fibreglass tape or glassfibre tape 52 mm
/ / Jointing powder (setting compound) bag EN 13963 / / Acrylic sealant
/ / Glasswool 70 mm 600 mm × 70 mm EN 13162 Air flow resistivity 5 kPa.s/m2 to 10 kPa.s/m2 NOTE The surface mass is determined by measuring the density in compliance with EN 520:2004+A1:2009, 5.11. SIST EN 16703:2015



EN 16703:2015 (E) 15
Key 1 plasterboard with tapered edge 2 U-70–30/6 Channel 3 C-70–35/6 Studs 4 screw 5 screw 6 self-adhesive fibreglass tape 7 jointing powder 8 acrylic sealant 9 glasswool 70 mm Figure B.1 — Sketch of the reference test partition 1 B.2 Installation procedure of partition Type 1 B.2.1 Installation of framework with channels and studs The framework consists of horizontal channels and vertical studs. 70 mm channels are fixed to the bottom and top of the aperture using screws and plastic plugs at nominal 500 mm centres, along the centre of the channel. The first and last fixing shall be located 100 mm from the corner. Please note that no material (foam strip, sealant etc.) shall be applied in between the channel web and the aperture. Channel joints shall be done as a butt joint i.e. the channels are put end to end (no overlap). There shall be a fixing at 100 mm from the joint, on both sides of the joint. Cut the studs so the length is 10 mm shorter than the height of the partition. Fix the first and last stud to the concrete frame of the aperture. The fixings of these studs are done in the same manner as for the channel i.e. using screws and plastic plugs at nominal 500 mm centres along the centre of the stud. The first and last fixing shall be located 100 mm from the corner. Please note that no material (foam strip, sealant etc.) shall be applied in between the stud web and the aperture. Place the remaining studs between top and bottom channel at 600 mm centres. In the starting side turn all the studs so that they have the web in the same direction as the first stud (excepted last stud that is in the opposite direction). The studs shall not be fixed to the top and bottom channels. The distance from the aperture to the first stud installed shall be 600 mm. To facilitate the installation of plasterboards, mark the position of the centre of the studs on the bottom and the top of the aperture. SIST EN 16703:2015



EN 16703:2015 (E) 16 B.2.2 Installation of plasterboards 1st side The plasterboards shall be cut so that there will be a 5 mm clearance on the lateral and top edges of the partition and a 5 mm to 10 mm clearance at the bottom. Cut vertical edges of plasterboards are only allowed on the first and last stud that is fixed to the aperture edges. All other vertical plasterboards edges shall be tapered edges. The plasterboards shall be butt-jointed i.e. without any gap between the tapered edges of the boards. Mark the positions of the screws on the board following the description below. When fully screwed the boards shall be screw fixed as follows: the screws along the edges of the board shall be 10 mm from the edge of the plasterboard. The boards shall be screw fixed into the edge studs and intermediate stud at 300 mm centres. The top and the bottom screw shall be located 100 mm from the top and the bottom end of the board. The board shall be fixed to the channel at top and bottom with one screw located half way between the studs and 15 mm from the board end. Before screw fixing the plasterboard make sure your screw driver
...

SLOVENSKI STANDARD
oSIST prEN 16703:2014
01-april-2014
$NXVWLND3UHVNXVQLSRVWRSHN]DVXKRPRQWDåQHVLVWHPHL]PDYþQRNDUWRQVNLK
SORãþVNRYLQVNRNRQVWUXNFLMR,]ROLUQRVWSUHG]YRNRPY]UDNX
Acoustics - Test code for drywall systems of plasterboard with steel studs - Airborne
sound insulation
Akustik - Prüfvorschrift für Trockenwandsysteme aus Metallständerwänden mit
Gipskartonbeplankung - Messung der Luftschalldämmung
Acoustique - Code d'essai pour systèmes de cloisons sèches en plaques de plâtre avec
montants en acier - Mesure de l'affaiblissement aérien
Ta slovenski standard je istoveten z: prEN 16703
ICS:
91.060.10 Stene. Predelne stene. Walls. Partitions. Facades
Fasade
91.120.20 $NXVWLNDYVWDYEDK=YRþQD Acoustics in building. Sound
L]RODFLMD insulation
oSIST prEN 16703:2014 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 16703:2014

---------------------- Page: 2 ----------------------
oSIST prEN 16703:2014

EUROPEAN STANDARD
DRAFT
prEN 16703
NORME EUROPÉENNE

EUROPÄISCHE NORM

January 2014
ICS 91.060.10; 91.120.20
English Version
Acoustics - Test code for drywall systems of plasterboard with
steel studs - Airborne sound insulation
Acoustique - Code d'essai pour systèmes de cloisons Akustik - Prüfvorschrift für Trockenwandsysteme aus
sèches en plaques de plâtre avec montants en acier - Metallständerwänden mit Gipskartonbeplankung - Messung
Mesure de l'affaiblissement aérien der Luftschalldämmung
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 126.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16703:2014 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
Contents
Foreword .3
Introduction .4
1 Scope .5
2 Normative references .5
3 Terms and definitions .5
4 Test code for drywall systems of plasterboard with steel studs .6
4.1 Application .6
4.2 Test element .6
4.3 Boundary and mounting conditions .6
4.3.1 General rules .6
4.3.2 Perimeters mounting .6
4.3.3 Partition positions .6
4.4 Test and operating conditions .7
4.4.1 Standard uncertainties .7
4.4.2 Diffusivity conditions .8
4.4.3 Flanking transmission .9
4.4.4 Reference partition Type 1 .9
4.5 Test report . 10
Annex A (normative) Reference partition Type 1 . 11
A.1 Description of Reference Partition Type 1 . 11
A.1.1 Single Framework, single board layer partition . 11
A.2 Installation procedure of partition Type 1 . 12
A.2.1 Installation of framework with channels and studs . 12
st
A.2.2 Installation of Plasterboards 1 side . 13
A.2.3 Installation of insulation in cavity . 13
nd
A.2.4 Installation of Plasterboards 2 side . 13
A.2.5 Jointing for both sides of the partition . 13
Annex B (normative) Reference partition Type 2 . 14
B.1 Twin framework, double board layer partition . 14
B.2 Installation of Plasterboards . 15
B.2.1 Plasterboard inner layer on first side . 16
B.2.2 Plasterboard outer layer on first side . 16
B.3 Installation of insulation in cavity . 16
nd
B.4 Installation of Plasterboards 2 side . 16
B.4.1 Plasterboard inner layer on second side . 16
B.5 Plasterboard outer layer on second side . 16
B.6 Jointing for both sides of the partition . 16
Annex C (normative) Test specimen location in aperture . 17
C.1 Case A "Aperture without niche and one acoustic break" . 17
C.2 Case B "Aperture without niche and two acoustic breaks with Ratio 2:1" . 17
C.3 Case C "Aperture with niche and one acoustic break with Ratio 2:1" . 17
Annex D (informative) Interlaboratory Tests performed for the development of this Test Code
standard . 19
Annex E (informative) E Modulus - Control Method (static E Modulus with 3 bending points) . 24
Annex F (informative) E Modulus - Expertise Method (dynamic E modulus). 25
Bibliography . 27

2

---------------------- Page: 4 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
Foreword
This document (prEN 16703:2014) has been prepared by Technical Committee CEN/TC 126 “Acoustic
properties of building elements and of buildings”, the secretariat of which is held by AFNOR.
This document is currently submitted to the CEN Enquiry.
This standard is a complement to the European Standard EN ISO 10140-1 and is not intended to replace it.
The complement includes more stringent rules, narrower tolerances and new, additional requirements.
3

---------------------- Page: 5 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
Introduction
Product standard EN 520 “Gypsum plasterboards – Definitions, requirements and test methods” specifies
requirements and test methods and establishes how to declare characteristics and to affix the CE marking of
products accordingly. In EN 520, when a drywall partition with plasterboard and steel studs has an airborne
sound insulation performance property, its sound reduction should be determined in accordance with
EN ISO 140-3, now replaced by EN ISO 10140-2 and EN ISO 717-1. The measured sound reductions are
calculated into sound reduction index R in third octave bands and into single number indexes, in accordance
,
with EN ISO 717-1. Those single number ratings are used for the CE marking.
Measurement of sound reduction according to EN ISO 10140-2 was known, through earlier interlaboratory
tests (ILT), to generate large spread in results from different laboratories. This was not suitable, either from a
competition point of view or from an end-user perspective. Therefore CEN/TC 126 “Acoustic properties of
building elements and of buildings” decided to set up a working group, WG 9 “Test Code for drywall partition
with plasterboard and steel studs”, with the scope to improve reproducibility by developing a Test Code. One
part of this work was to organize ILT for sound reduction measurements, to assess the uncertainty of acoustic
quantities. Then the working group prepared the test code presented in this standard that gives the level of
uncertainty of the acoustic measurement in laboratories of a drywall system of plasterboard with steel stud.
4

---------------------- Page: 6 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
1 Scope
This draft European Standard specifies additional information necessary to carry out efficiently and under
standardized conditions the determination of the sound reduction index of drywall systems of plasterboard
with steel studs according to EN ISO 10140-2 “Acoustics — Laboratory measurement of sound insulation of
building elements — Part 2: Measurement of airborne sound insulation”. It specifies the additional
requirements of the sound reduction measurements, the operating and mounting conditions that shall be used
for the test and additional test report information to be reported. Observe that all demands in EN ISO 10140-2
still must be fulfilled. The results obtained are used to convert frequency-dependent sound reduction index
into single number ratings, according to EN ISO 717-1. These performances can be used to compare different
products, or, and to express a requirement, or, and as input into estimation methods, such as the series
EN 12354-1.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 520, Gypsum plasterboards — Definitions, requirements and test methods.
EN 13162, Thermal insulation products for buildings — Factory made Mineral wool (MW) products —
Specification.
EN 13963, Jointing materials for gypsum plasterboards — Definitions, requirements and test methods.
EN 14195, Metal framing components for gypsum board systems — Definitions, requirements and test
methods.
EN 14566, Mechanical fasteners for gypsum plasterboard systems — Definitions, requirements and test
methods.
EN ISO 10140 (All parts), Acoustics — Laboratory measurement of sound insulation of building elements.
EN ISO 717-1, Acoustics — Rating of sound insulation in buildings and of building elements — Part 1:
Airborne sound insulation (ISO 717-1:2013).
EN 20140-2, Acoustics — Measurement of sound insulation in buildings and of building elements — Part 2:
Determination, verification and application of precision data (ISO°140-2:1991).
3 Terms and definitions
For the purposes of this document, the following term and definition apply.
3.1
drywall system of plasterboard with steel studs
partition comprising a rigid metal frame and enclosed by plasterboard
5

---------------------- Page: 7 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
4 Test code for drywall systems of plasterboard with steel studs
4.1 Application
4.1.1 This standard applies to non-load bearing metal frame partition comprising a rigid metal frame
enclosed by boards.
In general, the type, size, gauge and spacing of the studs, and the size, type and number of layers of
plasterboard and eventual amount and type of cavity filling material in partition constructions are determined
by the performance requirements of the system.
4.1.2 The quantity to be determined is the sound reduction index R as a function of frequency. The
definition of R is given in EN ISO 10140-2.
4.2 Test element
2 2
The test opening for walls should be 10 m (+/- 1 m ).
For all others information, refer to EN ISO 10140-2.
4.3 Boundary and mounting conditions
4.3.1 General rules
The test mounting should be mounted directly on the facilities frame; it cannot be a prefabricated full partition.
The test element should be installed in a similar manner to the actual construction with careful simulation of
typical connections and sealing conditions at the perimeter and at all joints.
4.3.2 Perimeters mounting
A gap of about 5 mm to 10 mm shall remain between the panel and the reveal of the test opening. This gap
shall be filled with appropriate material. Drying time has to respect product instruction according to 4.3.1. The
type of putty will have an influence on performance of the partition.
Cracks in the perimeter may occur, resulting in air leakage. A control procedure has to be set in laboratory to
avoid risk.
4.3.3 Partition positions
The sound reduction index of lightweight especially for twin leaf partitions (e.g. twin leaf gypsum board walls)
is influenced by the mounting conditions in the test opening of the laboratory. Important installation
parameters include the niche depth and the position of the partition in relation to the acoustic break in the test
aperture.
The partition shall be installed into the test opening so that the niches on both sides of the partition have
different depths with a ratio of 2:1.
To improve the reproducibility between laboratories and facilitate comparison of sound reduction indices for
different lightweight walls, the partition (even double wall) shall not be mounted across the acoustic break of
the laboratory, but on the same side of the break as indicated in Figure C.1 Partition example.
Main mounting conditions are reported in Annex C other may be used but shall be fully described in the test
report.
NOTE Mounting the lightweight partition with one leaf on one side and the other leaf on the other side of the acoustic
break can result in higher values for the sound reduction index.
Other mounting conditions may be suitable for certain types of twin leaf walls, for example, walls for
semidetached houses where the leaves are vibrationally uncoupled (for example on separate foundations). In
such cases the wall leaves can be mounted on each side of the acoustic break.
No absorption material should be located close (less than 1 meter) to the perimeter of the partition. The
acoustic break has to be covered with soft reflecting materials.
6

---------------------- Page: 8 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
4.4 Test and operating conditions
4.4.1 Standard uncertainties
To reduce expanded uncertainty in a reproducibility condition of drywall plasterboard partition with steel stud,
it is required to realize preliminary tests with two laboratory reference partitions described in Annexes A and B.
If the measured spectra fall within the envelopes presented below or the sum over all third octave bands of the
deviations between the measured and the envelope values does not exceed 4 dB it could be assumed that
the expanded uncertainty of R ; R + C and R + C of further measurements will be taken from Table 1.
w w w tr
The deviation of 4 dB has been decided to take into account of modal behaviours in low frequency but also for
the frequency where critical frequency has influenced the sound reduction. It has been observed both
laboratory configuration origin and panel stiffness. For the panel if critical frequency is not in the third octave
3150 Hz, it is recommended to control with the value of the E modulus to be at +/- 20% of what has been used
for the initial qualification of this method (see Annexes E and F)
Thanks to those preliminary tests, Table 1 and 2 could be used to give the standard uncertainties in a
reproducibility condition for airborne sound insulation in one third-octave bands are given and for different
single-number quantities.
Table 1 — Standard uncertainties by third octave bands
Standard uncertainty in a reproducibility
1/3 octave frequency band (f, Hz)
a
condition (u, dB)
50 2,5
63 3,1
80 2,7
100 1,8
125 1,6
160 1,0
200 1,0
250 0,8
315 1,1
400 0,9
500 0,7
630 1,2
800 1,5
1000 1,6
1250 2,2
1600 2,4
2000 2,2
2500 2,3
3150 1,5
4000 1,7
5000 2,1
a
Standard deviations determined by interlaboratory measurements (σ) served as an estimate
for the standard uncertainty.
7

---------------------- Page: 9 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
Table 2 — Standard uncertainties of single number quantities
Standard uncertainty
Single number
(dB)
Rw 0,7
R 0,7
w+C
R
w+ctr 1,1
For measurement results obtained in accordance with the ISO 140 series, the expanded uncertainty U shall
be calculated by:
U = k u
Where
u is the standard uncertainty determined in Table 1 and 2 of this standard; and
k is the coverage factor. Its value depends on the distribution of the possible values of the measurand
and on the confidence level.
For the purpose of this standard it is assumed that the values of the k is fixed at 2.
A measurement result shall then by stated as follows
Y= y ± U
Where
Y is the measurand, y the best estimate found by the measurement; and
U is the expanded uncertainty calculated for a given confidence level for the two-sided test 95 %.
For all other information refer to EN ISO 10140-2 and ISO 12999-1.
4.4.2 Diffusivity conditions
The diffusivity of the sound fields in the source and receiving room has been identified as one parameter that
can reduce the expanded uncertainty.
Large variations of the sound pressure level in the room indicate the presence of dominating strong standing
waves. EN ISO 10140-5 already imposes to have diffuse field conditions by proposing to install diffusing
elements in the rooms, it requires to ensure that the positioning and number of diffusing elements should be
arranged so that the sound reduction index is not influenced when further diffusing elements are installed.
In order to evaluate the diffuse field condition, put two additional simple diffusers as plasterboard panels (1,2 m x 2,4 m)
for each room (source and receiving room). Install them with two different slopes and according to the EN ISO 10140-5
section 3.2.2 specifications (minimum distance to microphone and loudspeaker and test specimen) preferably on the back
of the chamber.
To confirm the diffusivity, do the test with these two additional simple diffusers and check that results are
within the internal repeatability limits of the laboratory. Continue until results are inside the internal
repeatability of the laboratory. When necessary, add further diffusers.
8

---------------------- Page: 10 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
4.4.3 Flanking transmission
A sketch showing the different transmission paths between the rooms in a test facility is given in Figure 1.

Key
1 Source room
2 Receiving room
Dd Direct path
Fd, Ff and Df Flanking paths.
Figure 1 — Transmission path in a test facilities
EN ISO 10140-5 describes possible solutions to limit flanking transmission within the laboratory. Nevertheless,
inter laboratory test have showed that the evaluation of flanking transmission is very complex and are very
important for highly insulating lightweight constructions.
4.4.4 Reference partition Type 1
The Sound Reduction Index (SRI) of reference partition type 1 as described in Annex A; Figure A.1 shall be in
the range as given in Table 3.
9

---------------------- Page: 11 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
Table 3 — Sound reduction index of the reference partition type 1
frequency min value Average max value
(Hz) (dB) (dB) (dB)
50 10,3 15,9 21,5
63 8,9 14,2 19,5
80 8,1 12,55 17,0
100 12,3 14,55 16,8
125 20,1 22,55 25,0
160 27,9 30,05 32,2
200 32,2 33,7 35,2
250 34,0 36,3 38,6
315 38,3 40,25 42,2
400 42,2 44,1 46,0
500 44,9 47,4 49,9
630 47,2 49,7 52,2
800 49,6 52,7 55,8
1000 50,9 55,55 60,2
1250 51,5 57,25 63,0
1600 52,3 57,95 63,6
2000 51,2 56,05 60,9
2500 42,2 45,45 48,7
3150 39,9 42,35 44,8
4000 44,1 46,45 48,8
5000 47,4 49,9 52,4
4.5 Test report
The test report shall include the information listed in EN ISO 10140-2 and the following additional information
shall also be reported:
a) detailed description of the perimeters treatments;
b) detailed description of the putty used and its drying time;
c) detailed description of the fasteners used (screws spacing, stud centre) including perimeter frame;
d) detailed description of the partition position; refer to Annex C.
10

---------------------- Page: 12 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
Annex A
(normative)

Reference partition Type 1
A.1 Description of Reference Partition Type 1
A.1.1 Single Framework, single board layer partition
The partition consists of a 70 mm metal stud single framework with studs at 600 mm centres, 70 mm
insulation in the cavity and a single layer of 12,5 mm plasterboard on each side of the framework, see
Figure A.1. When acquiring the reference partition materials, the laboratory selects materials respecting the
reference properties presented in Table A.1.
If difficulty occurs it is suggested to refer to the local technical assistance of the manufacturer
Table A.1 — Material list and essential properties
Product Product
Product Dimensions Essential properties
number standard
1 Plasterboard with tapered edge 3000 x 1200 x EN 520 Surface mass [8,9;9,4] kg/m²
12,5 mm
2 U-70-30/6 Channel 30 x70 x 30 mm EN14195 Steel gauge [0,54;0,59] mm
3 C-70-35/6 Studs 34 x 69 x 36 mm EN14195 Steel gauge [0,54;0,59] mm
4 Self-tapping screw 3,5 x 25 mm EN 14566 / /
5 Plugs 6 x 60 mm / /
6 Self-adhesive fibreglass tape 52 mm / /
7 Jointing powder 25 kg EN13963 / /
8 Acrylic sealant  / /
9 Glasswool 70 mm 600 x 70 mm EN 13162 Air flow [5; 10]
resistivity
kPa.s/m²
11

---------------------- Page: 13 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)

Key
1 Plasterboard with tapered edge
2 U-70-30/6 Channel
3 C-70-35/6 Studs
4 Self-tapping screw
5 Plugs
6 Self-adhesive fibreglass tape
7 Jointing powder
8 Acrylic sealant
9 Glasswool 70 mm
Figure A.1 — Sketch of reference partition

A.2 Installation procedure of partition Type 1
A.2.1 Installation of framework with channels and studs
The framework consists of horizontal channels and vertical studs. 72 mm channels are fixed to the bottom and
top of the aperture using 44 mm screws and plastic plugs at nominal 500 mm centres, along the centre of the
channel. The first and last fixing should be located 100 mm from the corner. Please note that no material
(foam strip, sealant etc.) should be applied in between the channel web and the aperture. Channel joints
should be done as a butt joint i.e. the channels are put end to end (no overlap). There should be a fixing at
100 mm from the joint, on both sides of the joint. Cut the studs so the length is 10 mm shorter than the height
of the partition. Fix the first and last stud to the concrete frame of the aperture. The fixings of these studs are
done in the same manner as for the channel i.e. using 44 mm screws and plastic plugs at nominal 500 mm
centres along the centre of the stud. The first and last fixing should be located 100 mm from the corner.
Please note that no material (foam strip, sealant etc.) should be applied in between the stud web and the
aperture. Place the remaining studs between top and bottom channel at 600 mm centres. Start at side A and
turn all the studs so that they have the web in the same direction as the first stud (at side A). The studs should
not be fixed to the top and bottom channels. The distance from the aperture (at side A) to centre of the flange
of the second stud should be 600 mm. To facilitate the installation of plasterboards, mark the position of the
centre of the studs on the bottom and the top of the aperture.
12

---------------------- Page: 14 ----------------------
oSIST prEN 16703:2014
prEN 16703:2014 (E)
st
A.2.2 Installation of Plasterboards 1 side
The plasterboards should be cut so that there will be a 5 mm clearance on the lateral and top edges of the
partition and a 5 mm to 10 mm clearance at the bottom. Cut vertical edges of plasterboards are only allowed
on the first and last stud that is fixed to the aperture edges. All other vertical plasterboards edges should be
tapered edges. The plasterboards should be butt-jointed i.e. without any gap between the tapered edges of
the boards. Mark the positions of the screws on the board following the description below. When fully screwed
the boards should be screw fixed as follows: the screws along the edges of the board should be 10 mm from
the edge of the plasterboard. The boards should be screw fixed into the edge studs and intermediate stud at
300 mm centres. The top and the bottom screw should be located 100 mm from the top and the bottom end of
the board. The board should be fixed to the channel at top and bottom with one screw located half way
between the studs and 15 mm from the board end. Before screw fixing the plasterboard make sure your screw
driver is set so that the screw depth will be correct i.e. the screw head should be flush with the plasterboard.
The boards should be fixed using 25 mm screws. If by mistake, a screw is not catching the metal, the screw
should be removed and the hole later filled with jointing material. For the installation of plasterboards cut 5 mm
off the left hand edge of the first board (so that there will be a 5 mm clearance to the aperture on the left hand
side of the board and the right hand tapered edge of the board will be positioned at the middle of the flange of
the third stud). Stand the plasterboard on a 5 mm to 10 mm block to ensure the clearance of the bottom. To
ensure the verticality of the studs, only fix the board to the edge studs on the first side of the partition. Fixing to
the intermediate stud is done after board have been fixed at the second side of the partition. Install the
remaining boards
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.