Plugs, fixed or portable socket-outlets and appliance inlets for industrial purposes - Part 2: Dimensional compatibility requirements for pin and contact-tube accessories (IEC 60309-2:2021)

This document applies to plugs, fixed or portable socket-outlets, and appliance inlets,
hereinafter referred to as accessories, with a rated operating voltage not exceeding 1 000 V DC
or 1 000 V AC with a frequency not exceeding 500 Hz and a rated current not exceeding 125 A,
primarily intended for industrial use, either indoors or outdoors.
These accessories are intended to be installed by instructed persons or skilled persons only.
NOTE 1 All references for accessories with a rated current of more than 125 A in IEC 60309-1 are not applicable
to this document.
This document applies to accessories with pins and contact-tubes of standardized
configurations.
This document applies to accessories, for use when the ambient temperature is normally within
the range −25 °C to 40 °C.
The use of these accessories on building sites and for agricultural, commercial and domestic
applications is not precluded.
This document applies to accessories with screwless-type terminals or insulation piercing
terminals, with a rated current up to and including 32 A for series I and 30 A for series II.
Socket-outlets or appliance inlets incorporated in or fixed to electrical equipment are within the
scope of this document. This document also applies to accessories intended to be used in
extra-low voltage installations.
NOTE 2 This document does not apply to accessories primarily intended for domestic and similar general purposes.
In locations where special conditions prevail, for example on board ship or where explosions
are liable to occur, additional requirements can be necessary.

Stecker, ortsfeste oder ortsveränderliche Steckdosen und Gerätestecker für industrielle Anwendungen - Teil 2: Anforderungen an die maßliche Kompatibilität von Stift- und Buchsensteckvorrichtungen (IEC 60309-2:2021)

Fiches, socles fixes de prise de courant, prises mobiles et socles de connecteur pour usages industriels - Partie 2: Exigences dimensionnelles de compatibilité pour les appareils à broches et alvéoles (IEC 60309-2:2021)

L'IEC 60309-2:2021 s’applique aux fiches, socles fixes de prise de courant, prises mobiles et socles de connecteur, ci-après collectivement désignés par le terme "appareils", de tension nominale d’emploi ne dépassant pas 1 000 V en courant continu ou 1 000 V en courant alternatif, de fréquence ne dépassant pas 500 Hz, et de courant nominal ne dépassant pas 125 A, destinés essentiellement aux usages industriels, à l’intérieur ou à l’extérieur des bâtiments.
Cette cinquième édition annule et remplace la quatrième édition parue en 1999, son Amendement 1:2005 et son Amendement 2:2012. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l’édition précédente:


       
  1. ajout d’exigences et d’un essai pour les broches non massives;

  2.    
  3. ajout du degré de protection IPX9;

  4.    
  5. marquage supplémentaire pour indiquer la borne du neutre et/ou la borne de terre.


Le présent document est à lire conjointement avec l’IEC 60309-1:2021.

Vtiči, fiksne ali prenosne vtičnice in vtičnice za industrijsko rabo - 2. del: Zahteve za dimenzijsko skladnost pribora s trni in pušami (IEC 60309-2:2021)

General Information

Status
Published
Public Enquiry End Date
24-Oct-2019
Publication Date
13-Nov-2022
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
23-Jun-2022
Due Date
28-Aug-2022
Completion Date
14-Nov-2022

Relations

Buy Standard

Standard
EN IEC 60309-2:2022
English language
78 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN IEC 60309-2:2019
English language
72 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN IEC 60309-2:2022
01-december-2022
Nadomešča:
SIST EN 60309-2:2000
SIST EN 60309-2:2000/A1:2008
SIST EN 60309-2:2000/A11:2006
SIST EN 60309-2:2000/A2:2012
Vtiči, fiksne ali prenosne vtičnice in vtičnice za industrijsko rabo - 2. del: Zahteve
za dimenzijsko skladnost pribora s trni in pušami (IEC 60309-2:2021)
Plugs, fixed or portable socket-outlets and appliance inlets for industrial purposes - Part
2: Dimensional compatibility requirements for pin and contact-tube accessories
(IEC 60309-2:2021)
Stecker, ortsfeste oder ortsveränderliche Steckdosen und Gerätestecker für industrielle
Anwendungen - Teil 2: Anforderungen an die maßliche Kompatibilität von Stift- und
Buchsensteckvorrichtungen (IEC 60309-2:2021)
Fiches, socles fixes de prise de courant, prises mobiles et socles de connecteur pour
usages industriels - Partie 2: Exigences dimensionnelles de compatibilité pour les
appareils à broches et alvéoles (IEC 60309-2:2021)
Ta slovenski standard je istoveten z: EN IEC 60309-2:2022
ICS:
29.120.30 Vtiči, vtičnice, spojke Plugs, socket-outlets,
couplers
SIST EN IEC 60309-2:2022 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN IEC 60309-2:2022

---------------------- Page: 2 ----------------------
SIST EN IEC 60309-2:2022


EUROPEAN STANDARD EN IEC 60309-2

NORME EUROPÉENNE

EUROPÄISCHE NORM June 2022
ICS 29.120.30 Supersedes EN 60309-2:1999 + A1:2007 + A2:2012
English Version
Plugs, fixed or portable socket-outlets and appliance inlets for
industrial purposes - Part 2: Dimensional compatibility
requirements for pin and contact-tube accessories
(IEC 60309-2:2021)
Fiches, socles fixes de prise de courant, prises mobiles et Stecker, ortsfeste oder ortsveränderliche Steckdosen und
socles de connecteur pour usages industriels - Partie 2: Gerätestecker für industrielle Anwendungen - Teil 2:
Exigences dimensionnelles de compatibilité pour les Anforderungen an die maßliche Kompatibilität von Stift- und
appareils à broches et alvéoles Buchsensteckvorrichtungen
(IEC 60309-2:2021) (IEC 60309-2:2021)
This European Standard was approved by CENELEC on 2021-09-08. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN IEC 60309-2:2022 E

---------------------- Page: 3 ----------------------
SIST EN IEC 60309-2:2022
EN IEC 60309-2:2022 (E)
European foreword
The text of document 23H/481/FDIS, future edition 5 of IEC 60309-2, prepared by SC 23H "Plugs,
Socket-outlets and Couplers for industrial and similar applications, and for Electric Vehicles" of
IEC/TC 23 "Electrical accessories" was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN IEC 60309-2:2022.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022-12-17
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2025-06-17
document have to be withdrawn
This document supersedes EN 60309-2:1999 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document is read in conjunction with EN IEC 60309-1:2022.
This document has been prepared under a Standardization Request given to CENELEC by the
European Commission and the European Free Trade Association.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 60309-2:2021 was approved by CENELEC as a European
Standard without any modification.
2

---------------------- Page: 4 ----------------------
SIST EN IEC 60309-2:2022
EN IEC 60309-2:2022 (E)
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod),
the relevant EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Clause 2 of EN IEC 60309-1:2022 applies except as follows:
Add the following normative references:
Publication Year Title EN/HD Year
IEC 60309-1 2021 Plugs, fixed or portable socket-outlets and EN IEC 60309-1 2022
appliance inlets for industrial purposes -
Part 1: General requirements
IEC 60364-4-41 - Low-voltage electrical installations - Part 4- HD 60364-4-41 -
41: Protection for safety - Protection against
electric shock
3

---------------------- Page: 5 ----------------------
SIST EN IEC 60309-2:2022

---------------------- Page: 6 ----------------------
SIST EN IEC 60309-2:2022



IEC 60309-2

®


Edition 5.0 2021-06




INTERNATIONAL



STANDARD




NORME



INTERNATIONALE











Plugs, fixed or portable socket-outlets and appliance inlets for industrial

purposes –

Part 2: Dimensional compatibility requirements for pin and contact-tube


accessories



Fiches, socles fixes de prise de courant, prises mobiles et socles de connecteur


pour usages industriels –

Partie 2: Exigences dimensionnelles de compatibilité pour les appareils à

broches et alvéoles










INTERNATIONAL

ELECTROTECHNICAL

COMMISSION


COMMISSION

ELECTROTECHNIQUE


INTERNATIONALE




ICS 29.120.30 ISBN 978-2-8322-0000-0




Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 7 ----------------------
SIST EN IEC 60309-2:2022
– 2 – IEC 60309-2:2021 © IEC 2021
CONTENTS
FOREWORD . 5
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 8
4 General . 8
5 Standard ratings . 8
6 Classification of accessories . 9
7 Marking . 10
8 Dimensions. 12
8.2.1 General . 23
8.2.2 Checking plugs and appliance inlets . 24
8.2.3 Checking socket-outlets . 27
9 Protection against electric shock . 33
10 Provision for earthing . 33
11 Terminals and terminations . 33
12 Interlocks . 35
13 Resistance to ageing of rubber and thermoplastic material . 35
14 Construction . 35
15 Construction of fixed socket-outlets . 38
16 Construction of plugs and portable socket-outlets . 38
17 Construction of appliance inlets . 39
18 Degrees of protection . 39
19 Insulation resistance and dielectric strength . 39
20 Breaking capacity . 40
21 Normal operation . 40
22 Temperature rise . 40
23 Flexible cables and their connection . 40
24 Mechanical strength . 40
25 Screws, current-carrying parts and connections . 40
26 Creepage distances, clearances and distances through sealing compound . 41
27 Resistance to heat, to fire and to tracking . 41
28 Corrosion and resistance to rusting . 41
29 Conditional short-circuit current withstand test . 41
30 Electromagnetic compatibility . 41
Bibliography . 75

Figure 201 – 16/20 A, 32/30 A, 63/60 A and 125/100 A socket-outlets having rated
operating voltages exceeding 50 V – "go" gauges for checking dimensions d , d , l . 18
1 2 1
Figure 202 – 16/20 A, 32/30 A, 63/60 A and 125/100 A socket-outlets having rated
operating voltages exceeding 50 V – "no-go" gauges for checking dimensions d , d . 19
1 2

---------------------- Page: 8 ----------------------
SIST EN IEC 60309-2:2022
IEC 60309-2:2021 © IEC 2021 – 3 –
Figure 203 – 16/20 A, 32/30 A, 63/60 A and 125/100 A plugs and appliance inlets
having rated operating voltages exceeding 50 V – "go" gauges for checking
dimensions d , d , l . 20
2 4 1
Figure 204 – 16/20 A, 32/30 A, 63/60 A and 125/100 A plugs and appliance inlets
having rated operating voltages exceeding 50 V – "NO-GO" gauges for checking
dimensions d , d . 21
2 4
Figure 205 – 16/20 A and 32/30 A socket-outlets having rated operating voltages not

exceeding 50 V – Gauges for checking compatibility . 22
Figure 206 – 16/20 A and 32/30 A plugs and appliance inlets having rated operating
voltages not exceeding 50 V – Gauges for checking compatibility . 23
Figure 207 – "NO-GO" gauges for checking 16/20 A, 32/30 A, 63/60 A and 125/100 A
plugs and appliance inlets having rated operating voltages exceeding 50 V . 25
Figure 208 – 16/20 A and 32/30 A plugs and appliance inlets having rated operating
voltages not exceeding 50 V – Gauges for checking rigidity of enclosures of
thermoplastic material under humid and warm conditions . 25
Figure 209 – Device for testing non-solid pins . 27
Figure 210 – Arrangement for test using "NO-GO" gauge for checking 16/20 A,
32/30 A, 63/60 A and 125/100 A socket-outlets having rated operating voltages
exceeding 50 V . 29
Figure 211 – Gauges for checking socket-outlets of 16/20 A, 32/30 A, 63/60 A and
125/100 A having rated operating voltages exceeding 50 V . 30
Figure 212 – 16/20 A and 32/30 A socket-outlets having rated operating voltages not
exceeding 50 V – Gauges for checking rigidity of enclosures of thermoplastic material

under humid and warm conditions . 31
Figure 213 – Gauge for checking phase holes . 32
Figure 214 – Test of phase hole . 32
Figure 215 – Socket-outlets with enclosures of resilient or thermoplastic material –
Gauge for checking impossibility of single-pole insertion of a 10/16 A 250 V two-pole
plug 33
Figure 216 – Example of apparatus for checking the withdrawal force . 36


Table 201 – Rated currents . 9
Table 202 – Examples of marking for series I . 10
Table 203 – Examples of marking for series II . 10
Table 204 – Accessories with rated operating voltages exceeding 50 V . 13
Table 205 – Accessories with rated operating voltages not exceeding 50 V . 14
Table 206 – Retaining devices . 14
Table 207 – Forces applied to "GO"/"NO-GO" gauges . 15
Table 208 – General purpose accessories with rated operating voltage not exceeding
50 V 16
Table 209 – Special application accessories with rated operating voltage not
exceeding 50 V . 16
Table 210 – Positions of earthing contact . 16
Table 211 – Test forces . 24
Table 212 – Maximum displacement of the gauges . 28
Table 3 – Size of connectable conductors . 34
Table 213 – Pulling force on terminals . 34
Table 214 – Diameter of pins of the test plug . 35

---------------------- Page: 9 ----------------------
SIST EN IEC 60309-2:2022
– 4 – IEC 60309-2:2021 © IEC 2021
Table 215 – Maximum withdrawal forces . 36
Table 216 – Withdrawal forces . 37

---------------------- Page: 10 ----------------------
SIST EN IEC 60309-2:2022
IEC 60309-2:2021 © IEC 2021 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________

PLUGS, FIXED OR PORTABLE SOCKET-OUTLETS AND
APPLIANCE INLETS FOR INDUSTRIAL PURPOSES –

Part 2: Dimensional compatibility requirements
for pin and contact-tube accessories

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60309-2 has been prepared by subcommittee SC 23H: Plugs,
socket-outlets and couplers for industrial and similar applications, and for electric vehicles, of
IEC technical committee 23: Electrical accessories.
This fifth edition cancels and replaces the fourth edition published in 1999, Amendment 1:2005
and Amendment 2:2012. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) addition of requirements and test for non-solid pins;
b) additional rating IPX9;
c) additional marking to indicate neutral terminal and/or earthing terminal.

---------------------- Page: 11 ----------------------
SIST EN IEC 60309-2:2022
– 6 – IEC 60309-2:2021 © IEC 2021
The text of this International Standard is based on the following documents:
FDIS Report on voting
23H/481/FDIS 23H/487/RVD

Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/standardsdev/publications.
This document is to be read in conjunction with IEC 60309-1:2021.
In this document, the following print types are used:
– requirements proper: in roman type;
– test specifications: in italic type;
– notes: in smaller roman type.
IEC 60309-1:2021 deals with general requirements and comprises all clauses of a general
character.
Subsequent parts deal with the requirements of particular types of accessories. The clauses of
these particular requirements supplement or modify the corresponding clauses in
IEC 60309-1:2021.
Clauses, subclauses, figures, tables and notes which are additional to those in
IEC 60309-1:2021 are numbered starting from 201.
A list of all parts in the IEC 60309 series, published under the general title Plugs, fixed or
portable socket-outlets and appliance inlets for industrial purposes, can be found on the IEC
website.
Future standards in this series will carry the new general title as cited above. Titles of existing
standards in this series will be updated at the time of the next edition.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

---------------------- Page: 12 ----------------------
SIST EN IEC 60309-2:2022
IEC 60309-2:2021 © IEC 2021 – 7 –
PLUGS, FIXED OR PORTABLE SOCKET-OUTLETS AND
APPLIANCE INLETS FOR INDUSTRIAL PURPOSES –

Part 2: Dimensional compatibility requirements
for pin and contact-tube accessories



1 Scope
This document applies to plugs, fixed or portable socket-outlets, and appliance inlets,
hereinafter referred to as accessories, with a rated operating voltage not exceeding 1 000 V DC
or 1 000 V AC with a frequency not exceeding 500 Hz and a rated current not exceeding 125 A,
primarily intended for industrial use, either indoors or outdoors.
These accessories are intended to be installed by instructed persons or skilled persons only.
NOTE 1 All references for accessories with a rated current of more than 125 A in IEC 60309-1 are not applicable
to this document.
This document applies to accessories with pins and contact-tubes of standardized
configurations.
This document applies to accessories, for use when the ambient temperature is normally within
the range −25 °C to 40 °C.
The use of these accessories on building sites and for agricultural, commercial and domestic
applications is not precluded.
This document applies to accessories with screwless-type terminals or insulation piercing
terminals, with a rated current up to and including 32 A for series I and 30 A for series II.
Socket-outlets or appliance inlets incorporated in or fixed to electrical equipment are within the
scope of this document. This document also applies to accessories intended to be used in
extra-low voltage installations.
NOTE 2 This document does not apply to accessories primarily intended for domestic and similar general purposes.
In locations where special conditions prevail, for example on board ship or where explosions
are liable to occur, additional requirements can be necessary.
2 Normative references
Clause 2 of IEC 60309-1:2021 applies except as follows:
Additional normative references:
IEC 60309-1:2021, Plugs, fixed or portable socket-outlets and appliance inlets for industrial
purposes – Part 1: General requirements
IEC 60364-4-41, Low-voltage electrical installations – Part 4-41: Protection for safety –
Protection against electric shock

---------------------- Page: 13 ----------------------
SIST EN IEC 60309-2:2022
– 8 – IEC 60309-2:2021 © IEC 2021
3 Terms and definitions
Clause 3 of IEC 60309-1:2021 applies except as follows:
Additional terms and definitions:
3.201
phase inverter
plug or appliance inlet with operating means to interchange the position of two phase-pins
without disconnecting them from the conductors
3.202
solid pin
pin made from a single homogeneous material, without holes, slots, slits or similar outside the
terminal area
4 General
Clause 4 of IEC 60309-1:2020 applies except as follows:
4.1 Replace the fifth paragraph by the following:
In this document:
2P + E covers both 2P + E and 1P + N + E and
3P + E covers both 3P + E and 2P + N + E
unless specifically excluded (see Table 208).
Additional subclause:
4.201 If gauges are used, they shall be of hardened steel, all corners shall be slightly rounded-
off with a maximum radius of 0,1 mm and, if not otherwise specified, the surface finish for all
N8
measurement surfaces shall be minimum.
5 Standard ratings
Clause 5 of IEC 60309-1:2021 applies except as follows:

---------------------- Page: 14 ----------------------
SIST EN IEC 60309-2:2022
IEC 60309-2:2021 © IEC 2021 – 9 –
5.1 Replace the existing text with the following:
Preferred
rated operating voltage range
or rated operating voltage
20 V to 25 V
40 V to 50 V
100 V to 130 V
200 V to 250 V
277 V
380 V to 415 V
440 V to 460 V
480 V to 500 V
600 V to 690 V
750 V
1 000 V

5.2 Replace the existing text and Table 1 with the following:
Standard rated currents are given in Table 201.
Table 201 – Rated currents
Series I Series II
A A
16 20
32 30
63 60
125 100

Additional subclause:
5.201 The standard IP ratings according to IEC 60529 are:
– IP44,
– IP67,
– IP66/IP67,
– IP67/IP69,
– IP66/IP67/IP69.
6 Classification of accessories
Clause 6 of IEC 60309-1:2021 applies except as follows:
6.2 Not applicable.

---------------------- Page: 15 ----------------------
SIST EN IEC 60309-2:2022
– 10 – IEC 60309-2:2021 © IEC 2021
7 Marking
Clause 7 of IEC 60309-1:2021 applies except as follows:
7.1 Replace the sentence before the compliance statement at the end of the subclause by
the following paragraphs:
The symbol indicating the position of the earthing contact or of the minor key or keyway shall
be placed before or above the value for the rated operating voltage and separated from it by a
line.
These markings shall be placed after the marking for rated current, separated from it by a dash
if an oblique line separates the symbol indicating the position of the earthing contact or of the
minor key or keyway from the value for the rated operating voltage.
If a symbol for nature of supply is used, it shall be placed after or below the marking for rated
operating voltage.
For three-phase accessories it is not necessary to mark the voltage phase to neutral, if any.
The marking for rated current(s), position of the earthing contact or the minor key, keyway,
rated operating voltage(s) and nature of supply accordingly may be as follows.
Table 202 – Examples of marking for series I
9 h
16 –
16 A – 9 h/400 V~ 16 – 9 h/400~
400~
9 h
16
...

SLOVENSKI STANDARD
oSIST prEN IEC 60309-2:2019
01-oktober-2019
Vtiči, fiksne ali prenosne vtičnice in vtičnice za industrijsko rabo - 2. del: Zahteve
za dimenzijsko izmenljivost pribora s trni in pušami
Plugs, fixed or portable socket- outlets and appliance inlets for industrial purposes - Part
2: Dimensional interchangeability requirements for pin and contact-tube accessories
Stecker, Steckdosen und Kupplungen für industrielle Anwendungen - Teil 2:
Anforderungen und Hauptmaße für die Austauschbarkeit von Stift- und
Buchsensteckvorrichtungen
Prises de courant pour usages industriels - Partie 2: Règles d'interchangeabilité
dimensionnelle pour les appareils à broches et alvéoles
Ta slovenski standard je istoveten z: prEN IEC 60309-2:2019
ICS:
29.120.30 Vtiči, vtičnice, spojke Plugs, socket-outlets,
couplers
oSIST prEN IEC 60309-2:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN IEC 60309-2:2019

---------------------- Page: 2 ----------------------
oSIST prEN IEC 60309-2:2019


23H/457/CDV

COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 60309-2 ED5
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2019-08-09 2019-11-01
SUPERSEDES DOCUMENTS:
23H/432/CD,23H/453/CC

IEC SC 23H : PLUGS, SOCKET-OUTLETS AND COUPLERS FOR INDUSTRIAL AND SIMILAR APPLICATIONS, AND FOR ELECTRIC
VEHICLES
SECRETARIAT: SECRETARY:
France Mr Bertrand Doignon
OF INTEREST TO THE FOLLOWING COMMITTEES: PROPOSED HORIZONTAL STANDARD:


Other TC/SCs are requested to indicate their interest, if
any, in this CDV to the secretary.
FUNCTIONS CONCERNED:
EMC ENVIRONMENT QUALITY ASSURANCE SAFETY

SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.

This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.

TITLE:
Plugs, fixed or portable socket-outlets and appliance inelts for industrial purposes - Part 2:
Dimensional interchangeability requirements for pin and contact-tube accessories

PROPOSED STABILITY DATE: 2025

NOTE FROM TC/SC OFFICERS:


Copyright © 2019 International Electrotechnical Commission, IEC. All rights reserved. It is permitted to
download this electronic file, to make a copy and to print out the content for the sole purpose of preparing National
Committee positions. You may not copy or "mirror" the file or printed version of the document, or any part of it, for
any other purpose without permission in writing from IEC.

---------------------- Page: 3 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 2 23H/457/CDV

1 CONTENTS
2 FOREWORD . 3
3 INTRODUCTION . 5
4 1 Scope . 6
5 2 Normative references . 6
6 3 Terms and definitions . 6
7 4 General . 7
8 5 Standard ratings . 7
9 6 Classification . 8
10 7 Marking . 8
11 8 Dimensions . 11
12 9 Protection against electric shock . 30
13 10 Provision for earthing . 30
14 11 Terminals and terminations . 30
15 12 Interlocks . 32
16 13 Resistance to ageing of rubber and thermoplastic material . 32
17 14 Construction . 32
18 15 Construction of socket-outlets . 35
19 16 Construction of plugs and portable socket-outlets . 35
20 17 Construction of appliance inlets . 35
21 18 Degrees of protection . 36
22 19 Insulation resistance and dielectric strength . 36
23 20 Breaking capacity . 36
24 21 Normal operation . 36
25 22 Temperature rise . 37
26 23 Flexible cables and their connection . 37
27 24 Mechanical strength . 37
28 25 Screws, current-carrying parts and connections . 37
29 26 Creepage distances, clearances and distances through sealing compound . 37
30 27 Resistance to heat, to fire and to tracking . 37
31 28 Corrosion and resistance to rusting . 37
32 29 Conditional short-circuit current withstand test . 37
33 30 Electromagnetic compatibility . 37
34 bibliography . 72
35

---------------------- Page: 4 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 3 23H/457/CDV

36 INTERNATIONAL ELECTROTECHNICAL COMMISSION
37 ____________
38
39 PLUGS, FIXED OR PORTABLE SOCKET-OUTLETS AND APPLIANCE
40 INLETS
41 FOR INDUSTRIAL PURPOSES –
42
43 Part 2: Dimensional compatibility requirements
44 for pin and contact-tube accessories
45
46
47
48 FOREWORD
49 1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
50 all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
51 international co-operation on all questions concerning standardization in the electrical and electronic fields. To
52 this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
53 Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
54 Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
55 in the subject dealt with may participate in this preparatory work. International, governmental and non-
56 governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
57 with the International Organization for Standardization (ISO) in accordance with conditions determined by
58 agreement between the two organizations.
59 2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
60 consensus of opinion on the relevant subjects since each technical committee has representation from all
61 interested IEC National Committees.
62 3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
63 Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
64 Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
65 misinterpretation by any end user.
66 4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
67 transparently to the maximum extent possible in their national and regional publications. Any divergence
68 between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
69 the latter.
70 5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
71 assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
72 services carried out by independent certification bodies.
73 6) All users should ensure that they have the latest edition of this publication.
74 7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
75 members of its technical committees and IEC National Committees for any personal injury, property damage or
76 other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
77 expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
78 Publications.
79 8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
80 indispensable for the correct application of this publication.
81 9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
82 patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
83 International Standard IEC 60309-2 has been prepared by subcommittee SC 23H: Plugs,
84 socket-outlets and couplers for industrial and similar applications, and for electric vehicles, of
85 IEC technical committee 23: Electrical accessories.
86 This fifth edition cancels and replaces the fourth edition published in 1999, Amendment
87 1:[2005] and Amendment 2:[2012]. This edition constitutes a technical revision.
88 This edition includes the following significant technical changes with respect to the previous
89 edition:
90 a) addition of requirements and test for non-solid pins;
91 b) additional rating IPX9;
92 c) additional marking to indicate neutral terminal and/or earthing terminal.
93 The text of this International Standard is based on the following documents:

---------------------- Page: 5 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 4 23H/457/CDV

FDIS Report on voting
23H/---/FDIS 23H/---/RVD
94
95 Full information on the voting for the approval of this International Standard can be found in
96 the report on voting indicated in the above table.
97 This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
98 The committee has decided that the contents of the base publication and its amendments will
99 remain unchanged until the stability date indicated on the IEC web site under
100 "http://webstore.iec.ch" in the data related to the specific publication. At this date, the
101 publication will be
102 • reconfirmed,
103 • withdrawn,
104 • replaced by a revised edition, or
105 • amended.
106

---------------------- Page: 6 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 5 23H/457/CDV

107 INTRODUCTION
108
109 A list of all the parts in the IEC 60309 series, under the general title Plugs, fixed or portable
110 socket-outlets, and appliance inlets for industrial purposes, can be found on the IEC website.
111 Part 1 deals with general requirements and comprises all clauses of a general character.
112 Subsequent parts deal with the requirements of particular types of accessories. The clauses
113 of these particular requirements supplement or modify the corresponding clauses in Part 1.
114 In this standard, the following print types are used:
115 – requirements proper: in roman type;
116 – test specifications: in italic type;
117 – notes: in smaller roman type.
118

---------------------- Page: 7 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 6 23H/457/CDV

119 PLUGS, FIXED OR PORTABLE SOCKET-OUTLETS AND APPLIANCE
120 INLETS FOR INDUSTRIAL PURPOSES –
121
122 Part 2: Dimensional compatibility requirements for
123 pin and contact-tube accessories
124
125
126
127 1 Scope
128 This international standard applies to plugs, fixed or portable socket-outlets, and appliance
129 inlets, hereinafter referred to as accessories, with a rated operating voltage not exceeding
130 1 000 V DC or 1000 V AC not exceeding 500 Hz and a rated current not exceeding 125 A,
131 primarily intended for industrial use, either indoors or outdoors.
132 These accessories are intended to be installed by instructed persons (IEV 195-04-02) or
133 skilled persons (IEV 195-04-01) only.
134 NOTE 1 All references for accessories with a rated current of more than 125 A in part 1 are not applicable to this
135 part 2.
136 This standard applies to accessories with pins and contact-tubes of standardized
137 configurations.
138 This standard applies to accessories, for use when the ambient temperature is normally within
139 the range –25 °C to 40 °C.
140 The use of these accessories on building sites and for agricultural, commercial and domestic
141 applications is not precluded.
142 This standard applies to accessories with screwless type terminals or insulation piercing
143 terminals, with a rated current up to and including 32 A for series I and 30 A for series II.
144 Socket-outlets or appliance inlets incorporated in or fixed to electrical equipment are within
145 the scope of this standard. This standard also applies to accessories intended to be used in
146 extra-low voltage installations.
147 NOTE 2 This standard does not apply to accessories primarily intended for domestic and similar general
148 purposes.
149 In locations where special conditions prevail, for example on board ship or where explosions
150 are liable to occur, additional requirements may be necessary.
151 2 Normative references
152 Clause 2 of IEC 60309-1:2020 applies except as follows:
153 Additional normative references:
154 IEC 60364-4-41, Low-voltage electrical installations – Part 4-41: Protection for safety –
155 Protection against electric shock
156 IEC 60617-2, Graphical symbols for diagrams – Part 2: Symbol elements, qualifying symbols
157 and other symbols having general application
158 3 Terms and definitions
159 Clause 3 of IEC 60309-1:2020 applies except as follows:

---------------------- Page: 8 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 7 23H/457/CDV

160 Additional terms and definitions:
161 3. 201
162 phase inverter
163 a plug or an appliance inlet with operating means to interchange the position of two phase
164 pins without disconnecting them from the conductors
165 3.202
166 solid pin
167 pin made from a single homogeneous material, without holes, slots, slits or similar outside the
168 terminal area
169 4 General
170 Clause 4 of IEC 60309-1:2020 applies except as follows:
171 4.1 The last paragraph does not apply.
172 Add the following:
173 In this standard:
174 2P + E covers both 2P + E and 1P + N + E and
175 3P + E covers both 3P + E and 2P + N + E
176 unless specifically excluded (see Table 205).
177 Additional subclause:
178 4.201 If gauges are used, they shall be of hardened steel, all corners shall be slightly
179 rounded-off with a maximum radius of 0,1 mm, and the surface finish for all measurement
N8
180 surfaces shall be min., if not otherwise specified.
181 5 Standard ratings
182 Clause 5 of IEC 60309-1:2020 applies except as follows:
183 5.1 Replacement
Preferred
rated operating voltage range
or rated operating voltage
20 V to 25 V
40 V to 50 V
100 V to 130 V
200 V to 250 V
277 V
380 V to 415 V
440 V to 460 V
480 V to 500 V
600 V to 690 V
750 V
1 000 V
184
185 5.2 Replacement:
186 Standard rated currents are given in Table 201.

---------------------- Page: 9 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 8 23H/457/CDV

187 Table 201 – Rated currents
Series I Series II
A A
16 20
32 30
63 60
125 100
188
189 Additional subclause:
190 5.201 The standard IP ratings according to IEC 60529 are:
191 – IP44,
192 – IP67,
193 – IP66/IP67.
194 – IP67/IP69,
195 – IP66/IP67/IP69
196 6 Classification
197 Clause 6 of IEC 60309-1:2020 applies except as follows:
198 6.1.2 Not applicable.
199 7 Marking
200 Clause 7 of IEC 60309-1:2020 applies except as follows:
201 7.1 The note does not apply.
202 Additional paragraphs:
203 The symbol indicating the position of the earthing contact or of the minor key or keyway shall
204 be placed before or above the figure for the rated operating voltage and separated from it by
205 a line.
206 These markings shall be placed after that for rated current, separated from it by a dash if an
207 oblique line separates the symbol indicating the position of the earthing contact or of the
208 minor key or keyway from the figure for the rated operating voltage.
209 If a symbol for nature of supply is used, it shall be placed next to or below the marking for
210 rated operating voltage.
211 For three-phase accessories it is not necessary to mark the voltage phase to neutral, if any.
212 The marking for rated current(s), position of the earthing contact or the minor key, keyway,
213 rated operating voltage(s) and nature of supply accordingly may be as follows:
214

---------------------- Page: 10 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 9 23H/457/CDV

215 For series I:
9 h
16 -
16 A - 9 h/400 V~ 16 - 9 h/400~
400 ~
9 h
16 -
16 A - 9 h/380-415 V~ 16 - 9 h/380-415~
380 - 415 ~
6 h
32 A - 6 h/230/400 V~ 32 - 6 h/230/400~ 32 -
230 / 400 ~

6h
6 h / 220 / 380 V ~ 6 h / 220 / 380 ~

32
32 A - 32 -
200/346~
240 / 415 V ~ 240 / 415 V ~

240/415~

216
217 For series II
7 h
20 A - 7 h/480 V AC 20 A - 7 h/480~ 20 A -
480 ~
7 h
30 A -
30 A - 7 h/480 V 3 Phase, or 30 A - 7 h/480, 3Φ
480 V, 3Φ
7 h
60 A -
60 A - 7 h/277/480 V, 3 Phase Y 60 A - 7 h/277/480, 3ΦY
277 / 480 V, 3Φ Y
218 It is allowed to put the symbols for AC (~) [IEC 60417-5032 (2002-10)] and DC ( )
219 [IEC 60417-5031 (2002-10)] or ( ) [IEC 60417-5006 (2002-10)] after the values.
220 The drawings of standard sheets 2-I, 2-II, 2-III and 2-lV show accessories with the symbol 6 h
221 and those of standard sheets 2-VIII and 2-lX accessories with the symbol 12 h.
222 For accessories having rated operating voltages exceeding 50 V, the symbol indicating the
223 position of the earthing contact shall be a numeral followed by the letter h.
224 The numeral is derived from the position of the earth contact tube, when compared with the
225 face of a clock, the socket-outlet being viewed from the front with the keyway at the sixth
226 hour.
227 For accessories having rated operating voltages not exceeding 50 V, the symbol indicating
228 the position of the minor key shall be a numeral followed by the letter h.
229 The numeral is derived from the position of the minor key, when compared with the face of a
230 clock, the socket-outlet being viewed from the front with the major key at the sixth hour.
231 For plugs and appliance inlets, the symbol indicating the position of the earthing contact or
232 the minor keyway shall be the same as that for the corresponding socket-outlet.
233 Contact tubes of socket-outlets shall be positioned in the clockwise order when viewed from
234 the front as shown in the standard sheets (see also 7.5).
235 Pins of plugs and appliance inlets shall be positioned in the opposite order viewed from the
236 front.
237

---------------------- Page: 11 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 10 23H/457/CDV

238 7.4 Replacement
239 For plugs and portable socket-outlet, the marking specified in 7.1 shall be easily discernible
240 when the accessory is wired ready for use.
241 The marking for insulation voltage shall be on the main part; it shall not be visible when the
242 accessory is mounted and wired as in normal use.
243 NOTE 1 The term "ready for use" does not imply that the plug or portable socket-outlet is engaged with its
244 complementary accessory.
245 Compliance is checked by inspection.
246 7.5 Replacement
247 For rewirable accessories, the contacts shall be indicated by the following symbols.
248 – for accessories with three contacts (phase + neutral + earth, or, phase + phase + earth):
249 L / +, unmarked, (preferred) [IEC 60417-5019 (2006-08)] or [IEC 60417-5017
250 (2006-08)]
251 except for Series II clock position 4 h and 5 h which are marked:
252 N, unmarked, or
253 – for accessories with four contacts (three-phase + earth):
254 L1, L2, L3, or , or alternatively 1, 2, 3, or
255 except for Series II clock position 12 h (phase + centre tap + phase + earth) which is
256 marked:
257 L1, N, L2, or
258 – for accessories with five contacts (three-phase + neutral + earth):
259 L1, L2, L3, N, or , or alternatively 1, 2, 3, N or
260 – for accessories having a rated operating voltage not exceeding 50 V, 8 h clock position for
261 portable electric incubator: +12, +24.
262 These symbols shall be placed close to the relevant terminals; they shall not be placed on
263 screws, removable washers or other removable parts.
264 For phase inverters these symbols shall conform in one position with the requirements of 7.1.
265 In the other position of the inverting means, the phase marking need not conform.
266 Additional marking to indicate neutral terminal and/or earthing terminal may be used as
267 follows:
268 – letter W and/or white colour for neutral
269 – letter G and/or green colour for earthing
270 The terminals for pilot conductors are not required to be indicated. In the case they are
271 marked it is recommended to use the marking P or PILOT
272 The figures used with the letters may be written as an index. It is recommended that where
273 practicable the symbol be used.
274 Compliance is checked by inspection.
275 7.7 Addition:
276 The 2P + N + E, 12 h, Series II accessories shall use the indicating colour orange.

---------------------- Page: 12 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 11 23H/457/CDV

277 8 Dimensions
278 Clause 8 of IEC 60309-1:2020 applies except as follows:
279 8.1 Replacement:
280 Accessories shall comply with the relevant standard sheets as specified below:
281 – accessories having rated operating voltages exceeding 50 V:
Accessory Degree of protection Standard sheet
2-I
2-I continuation 1
IP44
2-II
2-II continuation 1
16/20 A and 32/30 A
IP67 2-I
IP67/IP69 2-I continuation 2
IP66/IP67 2-II
IP66/IP67/IP69 2-II continuation 2
2-III
2-III continuation 1
63/60 A, without pilot contact IP44
2-IV
2-IV continuation 1
IP67 2-III
63/60 A and 125/100 A, IP67/IP69 2-III continuation 2
without pilot contact IP66/IP67 2-IV
IP66/IP67/IP69 2-IV continuation 2
2-IIIa
2-III continuation 1
63/60 A, with pilot contact IP44
2-IVa
2-IV continuation 1
IP67 2-IIIa
63/60 A and 125/100 A, with IP67/IP69 2-III continuation 2
pilot contact IP66/IP67 2-IVa
IP66/IP67/IP69 2-IV continuation 2
IP44
IP67
Mechanical interlock for 16 A
IP67/IP69 2-V
to 125 A accessories
IP66/IP67
IP66/IP67/IP69
282
283 – accessories having rated operating voltages not exceeding 50 V:
Accessory Degree of protection Standard sheet
16/20 A and 32/30 A IP44 2-VIII
2-VIIIa
2-VIII continuation 1
2-IX
2-IXa
2-IX continuation 1
IP67 2-VIII
IP67/IP69 2-VIIIa
IP66/IP67 2-VIII continuation 2
IP66/IP67/IP69 2-IX
2-IXa
2-IX continuation 2
284

---------------------- Page: 13 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 12 23H/457/CDV

285 - retaining device as indicated in Table 209
286 Table 209 – Retaining devices
 Socket-outlets Plugs and appliance inlets
Rated Classification
Standard sheet Standard sheet
current according to
of the degree of
Rated Rated Rated Rated
accessory protection
Retaining Retaining
operating operating operating operating
against
means means
voltage voltage not voltage voltage not
A moisture
exceeding exceeding exceeding exceeding

50 V 50 V 50 V 50 V
IP44 Lid 2-II 2-IX
2-I 2-VIII Lug or cavity
(continuation 1) (continuation 1)
(continuation 1) (continuation 1)
16/20 and
32/30
IP66/IP67 Two-ramp Lug or cavity 2-II 2-IX
2-I 2-VIII
and IP67 system and bayonet (continuation 2) (continuation 2)
(continuation 2) (continuation 2)
ring
IP44 Lid and 2-IV –
2-III Lug or cavity
two-ramp – (continuation 1)
(continuation 1)
system
63/60
IP66/IP67 Two-ramp 2-III Bayonet ring 2-IV –

and IP67 system (continuation 2) (continuation 2)
IP66/IP67 Two-ramp 2-III Bayonet ring 2-IV –
125/100 –
a)
and IP67 system (continuation 2) (continuation 2)
a)
When 125/100 A fixed socket-outlets are mounted on or integrated with enclosures, the whole unit can also be IP44.
287 Deviations from the dimensions specified in the standard sheets may be made, but only if
288 they provide a technical advantage and do not adversely affect the purpose and safety of the
289 accessories complying with the standard sheets, especially with regard to compatibility and
290 non-compatibility.
291 Compliance is checked by means of gauges or by measurement for those dimensions not
292 covered by gauges,
293 – for accessories having rated operating voltages exceeding 50 V according to:
294 • Figures 201 and 202 for socket-outlets;
295 • Figures 203 and 204 for plugs and appliance inlets;
296 – for accessories having rated operating voltages not exceeding 50 V according to:
297 • Figures 205 and 206 for 16/20 A and 32/30 A accessories.
298 The gauges shall be moved axially to the centre line of the accessory with a force as shown in
299 the Table 202, applied for 1 min.
300 Table 202 – Forces applied to "GO"/"NO GO" gauges
Rated current
Rated operating Force (max.) for Force (max.) for
voltage "GO" gauge "NO GO" gauge
A
0
V Series I Series II N
N ( )
−1
Not exceeding 50 16 20 150 30
32 30 150 30
Exceeding 50 16 20 60 20
32 30 90 30
63 60 165 55
125 100 240 80
301 Before the test, the test specimen of insulating material shall be stored at a temperature of
302 (20 ± 5) °C and a relative humidity between 45 % and 75 % for four weeks.

---------------------- Page: 14 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2/Ed.5/CDV © IEC(E) 13 23H/457/CDV

303 For accessories having rated operating voltages not exceeding 50 V, the position of the minor
304 key or keyway shall be as shown in Tables 203-1 or 203-2
305 For accessories having rated operating voltages exceeding 50 V, the position of the earthing
306 contact shall be as shown in Table 205.
307 Compliance is checked by inspection.
308 Table 203 – General purpose accessories with rated operating voltage
309 not exceeding 50 V
Rated operating
Frequency Minor key or
voltage
a)
keyway position
V Hz
20 to 25 50 and 60 No minor key or keyway
40 to 50 50 and 60 12
100 up to and including 200 4
20 to 25 300 2
and 400 3
40 to 50 Over 400 up to and including 500 11
Direct current 10
a)
 The minor key or keyway position is indicated by the relevant number (see 7.1).
310
311 Table 204 – Special application accessories with rated operating voltage
312 not exceeding 50 V
Minor key or
Rated
Numbers of
keyway
operating Rated current Other characteristics and application
a)
poles
voltage
position
Portable electric incubators – use at 12 V DC or
25 V 32 A 3 8
24 V DC on ambulances or helicopters
a)
The minor key or keyway is indicated by the relevant number.
313
314 Positions 1 and 9 are reserved for future standardisation. For constructional reasons,
315 positions 5, 6 and 7 cannot be used.

---------------------- Page: 15 ----------------------
oSIST prEN IEC 60309-2:2019
60309-2
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.